+86-312-5959618  info@orionresistors.com
NGR Blog

How to Accurately Select the Insulation Level of a Neutral Grounding Resistor?

Writer: admin Time:2026-09-10 14:32:29 Browse:23℃

NGR Insulation Levels: Standards, Selection and Testing

Neutral grounding resistors (NGRs) are widely used in transformer and generator grounding systems to limit ground-fault current and reduce damage to windings, cores, cables, and other electrical equipment.

The insulation level of an NGR is an important part of its electrical design. It determines the required withstand voltage, insulation coordination, electrical clearance, creepage distance, and dielectric test requirements.

For international projects, NGR insulation should not be selected simply according to the system line voltage. The NGR rated voltage, applicable standards, system configuration, altitude, environmental conditions, and project requirements must all be considered.

1. What Is the Insulation Level of an NGR?

The insulation level of an NGR defines the voltage stresses that its insulation system is designed to withstand without electrical breakdown.

Typical insulation-related requirements include:

  • Power-frequency withstand voltage

  • Lightning impulse withstand voltage

  • Insulation resistance

  • Electrical clearance

  • Creepage distance

  • Insulation coordination

  • Environmental and altitude requirements

For an NGR directly connected between a transformer or generator neutral point and earth, the voltage across the resistor during a ground fault is primarily related to the system phase-to-neutral voltage.

Therefore, the NGR insulation rating should not automatically be equated with the system line-to-line voltage.

2. Which Standards Apply to NGR Insulation?

The following international standards may be relevant to NGR insulation design and testing:

Standard

Main Application

IEC 60076-25:2023

Dry-type neutral grounding resistors

IEC 60071-1:2019

Insulation coordination

IEC 60071-2

Application guidance for insulation coordination

IEC 60664-1

Insulation coordination for low-voltage equipment

IEC 60076-3

Transformer insulation and dielectric tests

IEEE C57.32 / IEEE C57.32a

Neutral grounding devices and related requirements where specified

For dry-type NGRs, IEC 60076-25:2023 is the most directly applicable IEC product standard.

The purchaser's specification should also be reviewed because additional or project-specific tests may be required.

11.jpg

3. How Is the NGR Rated Voltage Calculated?

For an NGR directly connected between the system neutral and earth, IEC 60076-25:2023 uses the phase-to-neutral voltage as the basis for determining the NGR rated voltage.

The basic relationship is:Ur = U / √3

Where:

  • Ur = NGR rated voltage

  • U = system nominal line-to-line voltage

For example, for a 13.8 kV system:

Ur = 13.8 kV / √3

Ur = 7.97 kV

The calculated NGR rated voltage is then used to select the applicable standard insulation level.

IEC 60076-25:2023 specifies that the selected Um should be equal to or higher than the calculated NGR rated voltage:

Um ≥ Ur

Therefore, for a 13.8 kV system:

Ur = 7.97 kV

The next applicable standard value is:

Um = 12 kV

Accordingly, the corresponding insulation values are:

  • Power-frequency withstand voltage: 28 kV RMS

  • Lightning impulse withstand voltage: 75 kV peak

  • Minimum air clearance: 120 mm

This is an important distinction when specifying NGR insulation for medium-voltage systems.

4. NGR Insulation Level Selection Table

The following table applies the IEC 60076-25:2023 selection principle:

Ur = U / √3

and then selects the next standard Um satisfying:

Um ≥ Ur

For systems below 1,000 V, IEC 60076-25:2023 refers to IEC 60664-1 for the applicable insulation coordination approach. Therefore, LV systems should not automatically be assigned the medium-voltage insulation values from the IEC 60076-25 table.

System Voltage U

NGR Rated Voltage Ur

Selected Um

Power-Frequency Withstand Ud

Lightning Impulse Withstand Up

Minimum Air Clearance

0.380 kV

0.219 kV

LV

See IEC 60664-1

See IEC 60664-1

Project dependent

0.400 kV

0.231 kV

LV

See IEC 60664-1

See IEC 60664-1

Project dependent

0.415 kV

0.240 kV

LV

See IEC 60664-1

See IEC 60664-1

Project dependent

0.480 kV

0.277 kV

LV

See IEC 60664-1

See IEC 60664-1

Project dependent

0.600 kV

0.346 kV

LV

See IEC 60664-1

See IEC 60664-1

Project dependent

0.690 kV

0.398 kV

LV

See IEC 60664-1

See IEC 60664-1

Project dependent

1.200 kV

0.693 kV

1.0 kV

2.2 kV RMS

12 kV peak

14 mm

2.400 kV

1.386 kV

3.6 kV

10 kV RMS

40 kV peak

60 mm

3.300 kV

1.905 kV

3.6 kV

10 kV RMS

40 kV peak

60 mm

3.600 kV

2.078 kV

3.6 kV

10 kV RMS

40 kV peak

60 mm

4.160 kV

2.402 kV

3.6 kV

10 kV RMS

40 kV peak

60 mm

6.300 kV

3.637 kV

7.2 kV

20 kV RMS

60 kV peak

90 mm

6.600 kV

3.811 kV

7.2 kV

20 kV RMS

60 kV peak

90 mm

7.200 kV

4.157 kV

7.2 kV

20 kV RMS

60 kV peak

90 mm

10.000 kV

5.774 kV

7.2 kV

20 kV RMS

60 kV peak

90 mm

11.000 kV

6.351 kV

7.2 kV

20 kV RMS

60 kV peak

90 mm

13.800 kV

7.967 kV

12 kV

28 kV RMS

75 kV peak

120 mm

14.400 kV

8.314 kV

12 kV

28 kV RMS

75 kV peak

120 mm

14.760 kV

8.521 kV

12 kV

28 kV RMS

75 kV peak

120 mm

15.000 kV

8.660 kV

12 kV

28 kV RMS

75 kV peak

120 mm

20.000 kV

11.547 kV

12 kV

28 kV RMS

75 kV peak

120 mm

22.000 kV

12.702 kV

17.5 kV

38 kV RMS

95 kV peak

160 mm

27.600 kV

15.935 kV

17.5 kV

38 kV RMS

95 kV peak

160 mm

34.500 kV

19.919 kV

24 kV

50 kV RMS

125 kV peak

220 mm

44.000 kV

25.403 kV

36 kV

70 kV RMS

170 kV peak

320 mm

66.000 kV

38.105 kV

52 kV

95 kV RMS

250 kV peak

480 mm

These values provide a useful reference for NGR insulation selection. The final design should always be verified against the applicable standard and project specification.

16.jpg

5. Standard NGR Insulation Levels

IEC 60076-25:2023 provides standardized insulation levels for NGRs.The principal values include:

Um

Power-Frequency Withstand Ud

Lightning Impulse Withstand Up

Minimum Air Clearance

1.0 kV

2.2 kV RMS

12 kV peak

14 mm

3.6 kV

10 kV RMS

40 kV peak

60 mm

7.2 kV

20 kV RMS

60 kV peak

90 mm

12 kV

28 kV RMS

75 kV peak

120 mm

17.5 kV

38 kV RMS

95 kV peak

160 mm

24 kV

50 kV RMS

125 kV peak

220 mm

36 kV

70 kV RMS

170 kV peak

320 mm

52 kV

95 kV RMS

250 kV peak

480 mm

72.5 kV

140 kV RMS

325 kV peak

630 mm

100 kV

185 kV RMS

450 kV peak

900 mm

123 kV

230 kV RMS

550 kV peak

1100 mm

145 kV

275 kV RMS

650 kV peak

1300 mm

170 kV

325 kV RMS

750 kV peak

1500 mm

245 kV

460 kV RMS

1050 kV peak

2100 mm

One important point is that Um in IEC 60076-25:2023 has an NGR-specific definition. It should not automatically be interpreted in exactly the same way as Um in other high-voltage equipment standards.

6. Example: 13.8 kV, 8 Ω, 1000 A NGR

Consider a neutral grounding resistor with the following specification:

Parameter

Value

System voltage

13.8 kV

NGR current

1,000 A

NGR resistance

8 Ω

Fault duration

15 s

First calculate the NGR rated voltage:

Ur = U / √3

Ur = 13.8 kV / √3

Ur = 7.97 kV

The selected standard insulation level must satisfy:

Um ≥ Ur

Therefore:

Um = 12 kV

The corresponding IEC 60076-25:2023 insulation values are:

Parameter

Value

Selected Um

12 kV

Power-frequency withstand Ud

12 kV RMS

Lightning impulse withstand Up

75 kV peak

Minimum air clearance

120 mm

The required resistance can be calculated from the phase-to-neutral voltage and the specified fault current:

R = Ur / I

Therefore:

R = 7.97 kV / 1,000 A

R ≈ 7.97 Ω

If the specified NGR resistance is 8 Ω, the actual fault current is approximately:

I = Ur / R

I = 7.97 kV / 8 Ω

I ≈ 996 A

This is consistent with a nominal 1,000 A NGR, subject to the specified resistance tolerance and actual system conditions.

1767954505208644.jpg

7. Insulation Resistance Test

Insulation resistance measurement is part of the routine test program for NGRs covered by IEC 60076-25:2023.

The test verifies the insulation condition between electrically live components and grounded components.

Typical measurement points may include:

  • NGR terminals to enclosure

  • Live resistor elements to earth

  • Insulated supports to grounded components

  • Neutral terminals to the enclosure

The actual test voltage and acceptance criterion should be specified according to the applicable standard and project requirements.

It is therefore not technically appropriate to state that every NGR must use a 2,500 V insulation resistance tester and achieve a universal minimum value such as 100 MΩ.

The correct acceptance criterion depends on the equipment design, applicable standard, manufacturer specification, and purchaser requirements.

8. Power-Frequency Withstand Voltage Test

The power-frequency withstand test verifies that the NGR insulation can withstand the specified AC test voltage without breakdown or flashover.

For example, if:

Um = 12 kV

the corresponding power-frequency withstand voltage is:

Ud = 28 kV RMS

The test is normally applied between the appropriate insulated electrical parts and earth or enclosure according to the standard test arrangement.

The test evaluates the integrity of:

  • Insulated neutral terminals

  • Terminal bushings

  • Insulated supports

  • Internal insulation

  • Barriers

  • Electrical connections

  • Insulation between energized components and the enclosure

The exact test duration and acceptance requirements should follow the applicable standard.

9. Lightning Impulse Withstand Test

Lightning impulse testing verifies the ability of the NGR insulation system to withstand transient overvoltages.

For:

Um = 12 kV

the corresponding lightning impulse withstand level is:

Up = 75 kV peak

However, lightning impulse testing should not be described as a mandatory routine test for every NGR.

Under IEC 60076-25:2023, lightning impulse testing is classified as a special test.

It may be required when specified by:

  • The purchaser

  • The project technical specification

  • The insulation coordination study

  • The system voltage level

  • The installation environment

  • The applicable utility standard

10. Electrical Clearance and Creepage Distance

Electrical clearance is the shortest distance through air between conductive parts at different electrical potentials.

Creepage distance is the shortest distance along the surface of an insulating material.

Both parameters are important in NGR design.

For example, when:

Um = 12 kV

IEC 60076-25:2023 specifies a minimum air clearance of:

120 mm

However, the final design may require a larger clearance depending on:

  • Installation altitude

  • Pollution level

  • Indoor or outdoor installation

  • Humidity

  • Insulating material

  • Surface contamination

  • Transient overvoltage

  • Project requirements

Therefore, the standard minimum clearance should not automatically be treated as the final physical dimension of every NGR enclosure.

1759215589578808.jpg

11. Altitude and Environmental Conditions

Altitude affects the dielectric strength of air.

As altitude increases, the insulation strength of air decreases. Consequently, equipment installed at high altitude may require increased electrical clearance or other insulation coordination measures.

For installations above 1,000 m, the insulation requirements should be evaluated using the applicable guidance in IEC 60071-2.

An NGR installed at a high-altitude power plant may therefore require:

  • Increased air clearance

  • Increased creepage distance

  • Higher insulation level

  • Modified enclosure construction

  • Additional environmental protection

The installation altitude should therefore be clearly stated in the NGR technical specification.

12. NGR Insulation Tests and Test Classification

IEC 60076-25:2023 separates NGR tests into routine tests, type tests, and special tests.

Test

Classification

Visual and dimensional inspection

Routine Test

Rated resistance measurement

Routine Test

Power-frequency withstand voltage test

Routine Test

Insulation resistance measurement

Routine Test

Temperature-rise test

Type Test

Inductance measurement

Special Test

Lightning impulse test

Special Test

Mechanical design verification

Special Test

Degree-of-protection test

Special Test

This classification is important when preparing a factory test plan.

For example, lightning impulse testing and IP degree-of-protection testing should not automatically be presented as mandatory type tests for every NGR.

They are special tests under IEC 60076-25:2023 and should be included when required by the project or purchaser.

13. Temperature Rise and NGR Insulation Design

The insulation system of an NGR is closely related to its thermal design.

During a ground fault, the resistor elements can reach a high temperature depending on the fault current and duration.

IEC 60076-25:2023 specifies maximum temperature-rise values for resistive elements according to the operating duty:

NGR Duty

Maximum Temperature Rise of Resistive Elements

Rated time ≤ 60 s

760 K

Extended time < 10 min

610 K

Continuous duty

385 K

Temperature rise and absolute temperature are different concepts.

For example:

ΔT = 760 K

means a temperature rise of 760 K above the reference temperature. It does not mean that the resistor element is operating at exactly 760 °C.

The actual element temperature depends on the initial temperature and operating conditions.

NGR thermal design should consider:

  • Resistor element material

  • Resistance value

  • Fault current

  • Fault duration

  • Thermal capacity

  • Ventilation

  • Enclosure construction

  • Insulating materials

  • Terminal temperature

  • Adjacent component temperature

Electrical insulation and thermal performance should therefore be evaluated together.


14. What About 380 V to 690 V NGRs?

Low-voltage NGRs are used in applications such as:

  • Generator auxiliary systems

  • Industrial power systems

  • Mining power systems

  • Motor systems

  • Plant auxiliary transformers

  • Low-voltage generator systems

Common system voltages include:

System Voltage

Equivalent in kV

380 V

0.380 kV

400 V

0.400 kV

415 V

0.415 kV

480 V

0.480 kV

600 V

0.600 kV

690 V

0.690 kV

These systems are below 1,000 V.

Therefore, the insulation coordination approach should consider IEC 60664-1 and the actual low-voltage equipment design rather than directly applying the medium-voltage insulation table from IEC 60076-25:2023.

For example, for a 400 V system:

Ur = 400 V / √3

Ur ≈ 231 V

This calculation does not mean that the NGR should automatically be assigned the 1.0 kV insulation level from the IEC 60076-25 table.

The final insulation design depends on factors such as:

  • Overvoltage category

  • Pollution degree

  • Clearance

  • Creepage distance

  • Insulation material

  • Working voltage

  • Transient overvoltage

  • Equipment construction

  • Applicable project requirements

15. Practical NGR Insulation Selection Procedure

A practical engineering procedure can be summarized as follows.

Step 1: Determine the system voltage

Identify the nominal line-to-line system voltage.

Example:

U = 13.8 kV

Step 2: Calculate the NGR rated voltage

For a directly connected neutral grounding resistor:

Ur = U / √3

Therefore:

Ur = 13.8 / √3 = 7.97 kV

Step 3: Identify the applicable standard

For a dry-type NGR, check IEC 60076-25:2023.

For systems below 1,000 V, also consider IEC 60664-1 and the applicable low-voltage requirements.

Step 4: Select the standard Um

Select the next standard value satisfying:

Um ≥ Ur

For a 13.8 kV system:

Ur = 7.97 kV

Therefore:

Um = 12 kV

Step 5: Determine the withstand levels

For Um = 12 kV:

Ud = 28 kV RMS

Up = 75 kV peak

Step 6: Check electrical clearance

For Um = 12 kV:

Minimum air clearance = 120 mm

Then determine whether additional clearance or creepage distance is required.

Step 7: Review environmental conditions

Check:

  • Installation altitude

  • Indoor or outdoor installation

  • Pollution level

  • Ambient temperature

  • Humidity

  • Seismic requirements where applicable

Step 8: Define the factory test program

Separate the tests into:

  • Routine Tests

  • Type Tests

  • Special Tests

This approach provides a clearer and more defensible technical specification for an NGR.

16. Common Mistakes in NGR Insulation Selection

Mistake 1: Using the system line voltage directly

An incorrect approach would be:

13.8 kV system → 13.8 kV NGR rated voltage

For a directly connected NGR, the initial calculation is:

Ur = 13.8 / √3 = 7.97 kV

The appropriate standard Um is then selected based on:

Um ≥ Ur

which gives:

Um = 12 kV

Mistake 2: Treating lightning impulse testing as a routine test

Lightning impulse testing is a special test under IEC 60076-25:2023.

It should be specified when required by the project or insulation coordination requirements.

Mistake 3: Applying one insulation resistance limit to every NGR

A universal requirement such as:

Insulation resistance ≥ 100 MΩ

should not be presented as an IEC 60076-25 requirement for every NGR.

The test voltage and acceptance criterion should be established according to the applicable standard and project specification.

Mistake 4: Ignoring altitude

Air insulation strength decreases with increasing altitude.

High-altitude installations may therefore require additional insulation coordination measures.

Mistake 5: Confusing resistance tolerance with temperature-related resistance change

The rated resistance tolerance and the resistance change caused by heating are different technical requirements.

For example, an NGR may have a specified rated resistance tolerance:

R ± 10%

while its resistance variation during the temperature-rise test is evaluated separately.

These two requirements should not be treated as the same parameter.

17. Conclusion

NGR insulation selection should be based on the actual neutral-to-earth voltage, the applicable product standard, insulation coordination, and installation conditions.

For a directly connected NGR covered by IEC 60076-25:2023, the basic relationship is:

Ur = U / √3

The calculated Ur is then used to select the next applicable standard value satisfying:

Um ≥ Ur

For example, for a 13.8 kV system:

Ur = 13.8 / √3 = 7.97 kV

Therefore:

Um = 12 kV

The corresponding insulation levels are:

Ud = 28 kV RMS

Up = 75 kV peak

Minimum air clearance = 120 mm

For low-voltage systems such as 380 V, 400 V, 415 V, 480 V, 600 V, and 690 V, the insulation coordination approach should consider IEC 60664-1 and the actual equipment design rather than directly applying the medium-voltage NGR insulation table.

A properly designed NGR should integrate electrical, thermal, mechanical, environmental, and insulation requirements. Selecting the insulation level from the system voltage alone is not sufficient for a reliable international NGR specification.







Previous:What Are the NGR Type Tests and Standards? Next:no more