+86-312-5959618  info@orionresistors.com

Neutral Grounding Resistor for Transformer

  • Neutral Grounding Resistor for Transformer
  • Neutral Grounding Resistor for Transformer
  • Neutral Grounding Resistor for Transformer
  • Neutral Grounding Resistor for Transformer

Transformer Neutral Grounding Resistor

  • Product Feature:The OR-TN series Neutral Grounding Resistor (NGR) Cabinet is a specialized device that safely grounds transformer neutrals in 6-66kV systems. It limits fault current to protect equipment from dangerous overvoltages, suppresses electrical arcs, and ensures system stability. Its robust design features high-temperature resistant resistors, an intelligent controller for continuous monitoring, and a corrosion-resistant cabinet for reliable operation in demanding environments.
  • INQUIRY

Overview

Under normal conditions, the three-phase neutral point of a generator or transformer remains balanced, with its potential close to zero. The neutral point acts as the system's reference, maintaining voltage symmetry and providing a controlled grounding path. If the neutral insulation is damaged, the grounding resistor becomes open-circuited, or unintended grounding occurs, the system loses itsvoltage reference. This leads to phase voltage imbalance (one phase may rise to line voltage level) causing insulation over-stress, partial discharge, or equipment damage. Conversely, if the neutral point is short-circuited or the grounding resistor fails, the single-phase fault current can surge, resulting in false protection trips, overheating, or even winding burnout. Severe conditions may cause arc grounding, secondary over-voltage, and cascading trips, threatening overall system stability.

transformer generator neutral accident(1).jpg

To prevent such hazards, transformer neutral grounding ensures safe and reliable system operation by stabilizing voltage, limiting overvoltage, and enabling fault protections in low-, medium-, and high-voltage networks. When a single-phase-to-ground fault occurs, grounding forms a loop through the phase conductor, ground, and neutral point, generating sufficient current to activate protective relays and isolate the fault. Neutral grounding also provides a discharge path for lightning and switching surges, thereby protecting insulation and extending equipment lifespan.The Neutral Grounding Resistor (NGR) cabinet fulfills these functions by inserting a resistor between the neutral and ground. It limits fault current to a safe level while ensuring accurate relay operation, achieving an effective balance between protection sensitivity and system safety.


ezgif-23e356a0e6a4ff.gif

The OR-TN Series Transformer Neutral Grounding Resistor Cabinet, developed by ORION RESISTOR, is a complete set of specialized equipment designed specifically for transformer neutral grounding applications. It includes both High Resistance Grounding (HRG) and Low Resistance Grounding (LRG) systems, suitable for installation in 6–66 kV power generation auxiliary systems, substation distribution networks, and industrial or mining cable systems, providing a stable and secure neutral grounding solution for power systems.

The High Resistance Grounding (HRG) system is typically used in low-voltage systems (≤1 kV) or medium-voltage distribution networks (3.3–6.6 kV), such as mines, data centers, and factories. Its main feature is that the ground fault current is limited to 5–10 A, helping to prevent system shutdowns and facilitate single-phase fault location.

The Low Resistance Grounding (LRG) system is mainly applied to high-voltage generator and transformer systems (6.6–35 kV), such as powerstations, petrochemical facilities, and heavy industrial networks. The ground fault current typically ranges from 100 A to 1000 A, ensuring sufficient current for protective devices to operate effectively and quickly isolate faults.

10 Key Parameters for Selecting Neutral Grounding Resistors (NGR).

How to Accurately Calculate the Neutral Grounding Resistance Value of a Transformer?

Solid, Resistance, and Ungrounded Systems — Which Is Safer for your Network?

The Most Comprehensive Reference of Grounding Currents and Resistor Values under Different System Voltages

Global Top 8 Neutral Grounding Resistor (NGR)Manufacturers


Star-Connected Transformer Neutral Grounding Diagram:  

    1758863214844669.jpg



Delta-Connected Transformer Neutral Grounding Diagram:

Since a delta-connected winding does not provide a neutral point, a grounding transformer (typically with a Δ-Y connection) is employed. The transformer secondary is derived and converted into a star configuration to obtain a neutral point, which is then connected to the neutral grounding resistor through the grounding resistor cabinet, as illustrated in the diagram.

1758854682544796.jpg

Functional Features of OR-TN Resistor:

1. Resistor element: Made of high-quality non-metallic special materials or nickel-chromium alloy with stainless steel, ensuring stable resistance, high conductivity, strong current-carrying capacity, high-temperature endurance, and flameproof and explosion-proof performance.

2. Cabinet structure: Designed primarily for indoor use, fabricated from powder-coated cold-rolled steel plates or stainless steel, providing corrosion resistance and a high degree of protection.

3. Intelligent controller: Capable of monitoring and recording system zero-sequence current under normal conditions, single-phase ground fault current, grounding duration, system zero-sequence voltage, resistor temperature, as well as ambient temperature and humidity inside the cabinet. It also records the number of grounding operations.

4. Alarm and protection functions: Provides system grounding alarm, ambient over-temperature trip and alarm, resistor over-temperature trip and alarm, resistor open-circuit monitoring alarm, and grounding overtime protection and alarm.

5. Communication interface: Equipped with a communication port to transmit recorded data to the main control room for upper-level computer communication.

Technical Parameters:

1. Recommended Technical Parameter Table (OR-TN Series)

Model

System Rated 

Voltage  (kV)

Rated Voltage (L-N)

 (kV)

Current Ratings (A)

Rated Time (s)

 Resistance at 25℃

(Ω, ±5%)

OR-TN6.3–100–10

6.3

3.64

100

10

36.4

OR-TN6.3–600–10

6.3

3.64

600

10

6.0

ORTN10.5–200–10

10.5

6.0

200

10

30

ORTN10.5–400–10

10.5

6.0

400

10

15

ORTN10.5–600–10

10.5

6.0

600

10

10

OR-TN10.5–1000–10

10.5

6.0

1000

10

6

OR-TN35–400–10

35

20

400

10

50

OR-TN35–600–10

35

20

600

10

33.3

OR-TN35–800–10

35

20

800

10

25

OR-TN35–1000–10

35

20

1000

10

20


neutral grouding resistor construction-80.jpg



Orion Resistors adopt Fe-Cr-Al stainless steel or Ni-Cr grid resistor elements, featuring excellent stability, high temperature resistance, dense oxide film, and long service life.

resistor(1).jpg



All Orion Resistors use high-quality circuit breakers, relays, and surge protectors, combined with intelligent control to ensure coordinated operation and accurate fault current limitation.

orion resistor components.jpg


Why Choose Orion Resistor?

1.High-capacity workshops and standardized assembly lines ensure every grounding resistor meets international performance standards.

why Orion-1(1).jpg


2.Every resistor and transformer is built with strict quality control and premium materials for long-term reliability.

why Orion-2(1).jpg


3.Comprehensive design verification and high-voltage testing guarantee safety and performance before delivery.

why Orion-3(1).jpg


4.Each NGR cabinet is vacuum-sealed to prevent moisture ingress during transport, ensuring stable insulation resistance and reliable electrical performance upon delivery.

出口真空包装8(1).jpg


     Field photos from customer sites, covering substations, power plants, data centers, mining operations, and photovoltaic systems

istockphoto-1179604142-170667a.jpg

Neutral Grounding Resistor FAQ:

1. How to determine the correct grounding resistance value?

Core Standard: IEEE Std 32 / IEC 60071-1
The grounding resistance value must balance fault limitation and protection sensitivity. Incorrect selection may cause either excessive fault current or delayed protection operation.
Formula:

R=UL3×Iset

  • ULU_{ph}: Line voltage or system voltage

  • IsetI_{set}: Protection current setting (typically 200–1000 A)

Example:
For a 10 kV system with a 500 A target fault current,

R=100001.732×50011.54ΩR = rac{5770}{1.732 imes 500} ≈ 6.7 Ω

In practice, 12 Ω is commonly used to align with standard resistor element series.
Verification: Neutral-point voltage displacement ≤ 10 % of phase voltage; steady-state temperature rise within rated limits.

2. How to select the thermal withstand time (time rating)?

Core Standard: IEEE Std C37.101 / IEC 60909
Thermal capacity must match the system’s protection coordination:

  • Typical distribution networks: Protection clears within 0.2 s → 10 s rating recommended (per IEC type test, 1000 A × 10 s = 5 MJ).

  • Critical loads (data centers, hospitals): With delayed backup protection (2–3 s), select ≥ 5 s models.
    Tip: Certified NGRs clearly mark “1000 A / 10 s” or equivalent; uncertified products may omit this parameter.

3. Which resistor element material ensures long-term stability?

Core Standard: ASTM B344 / IEC 60115
Material determines both lifespan and temperature coefficient:

  • Nickel-Chromium Alloy (NiCr): Temp. coefficient ≤ 50 ppm/°C; withstands 760 K rise for 10–60 s; lifespan > 20 years.

  • Stainless Steel (304/316L): High corrosion resistance, especially for marine or chemical sites.

  • Carbon Steel: Low cost but poor oxidation resistance; resistance drift or fuse risk after 1–2 years.
    Recommendation:

  • Indoor/industrial: NiCr alloy balance of cost and performance.

  • Marine/chemical: 316L stainless steel for corrosion protection.

4. What protection and monitoring functions are essential?

Core Standard: IEC 60255 / IEC 61850
Modern NGR systems must integrate both protective interlocks and remote supervision:

  • Basic Protections:

    • Overcurrent trip (aligned with Iset)

    • Overtemperature alarm (≥ 300 °C)

    • Door/isolator interlock

  • Smart Monitoring:

    • Current + temperature sensors

    • RS485 / Modbus-RTU communication

    • SCADA integration (fault current waveform & temperature trend)

  • Advanced Options:

    • Fault counter, remote ON/OFF, event log for predictive maintenance.

5. What insulation level and clearance are required for safety?

Core Standard: IEC 60071-1 / IEC 62271-200 / IEEE Std 32
Insulation and creepage design ensure reliability under environmental stress:

  • For 10 kV systems:

    • Creepage ≥ 250 mm

    • Phase-to-earth insulation ≥ 1000 MΩ (2.5 kV megger)

    • Phase spacing ≥ 125 mm

  • Enclosure protection:

    • Standard type: IP55 (industrial)

    • Enhanced type: IP65 (mining, offshore)

  • Material:

    • 304/316L stainless steel (≥ 15 yrs anti-corrosion)

    • Hot-dip galvanized steel (zinc ≥ 85 µm, 10 yrs + durability)

  • Explosion-proof option: IEC 60079-1 compliant design.

6. How to select the right NGR for high-resistance vs. low-resistance grounding systems?

Core Standard: IEEE Std 142 (Green Book) / IEC 60071

  • High-Resistance Systems:
    1 kΩ – 2 kΩ range, fault current ≤ 10 A; ideal for data centers & hospitals.
    Use ±1 % precision metal film resistors.

  • Low-Resistance Systems:
    5 Ω – 50 Ω range, fault current 50 – 1000 A; used in industrial grids.
    Use wire-wound resistors ≥ 5 kW.

  • Hybrid Systems:
    With arc-suppression coil + resistor combination; short-time impulse type required, ensuring “arc extinction before resistor insertion.”

7. How does installation environment affect NGR design?

Core Standard: IEC 60529 / IEC 60068
Environment determines enclosure and cooling method:

  • Outdoor / humid: IP54–IP65, sealed cabinet with anti-condensation heater.

  • Indoor / control room: IP30 adequate, ≥ 5 kW units require forced air cooling + fan fault alarm.

  • High altitude: Increase insulation rating by 10 % per 1000 m.

8. What about system protection coordination and relay settings?

Core Standard: IEC 60255-151 / IEEE C37.101
Changing to an NGR (low-resistance grounding) requires relay coordination:

  • Enable zero-sequence protection.

  • Adjust pickup ≤ 300 A to coordinate with upstream grid.
    Failure to adjust may cause unwanted feeder tripping during faults.

9. Any special considerations for systems with distributed generation (e.g. solar, wind)?

Core Standard: IEC 61727 / IEEE 1547
Distributed sources may alter fault current direction.
Check inverter fault contribution and ensure directional earth-fault relays are used to avoid mal-operation.

10. How to design NGRs for Δ-connected transformers without a neutral point?

Core Standard: IEEE Std 32 / IEC 60076-3
Use a Z-type grounding transformer + NGR combination:

  • Grounding transformer capacity ≈ (system capacitive current × 10 kV) → e.g. 25 A → 250 kVA.

  • Zero-sequence impedance ≤ 5 Ω.

  • No-load loss ≤ 0.5 %; negligible under normal operation.

  • Verify thermal coordination between the grounding transformer and resistor assembly.

11. How should the residual current device (RCD/ELCB) be selected for client protection?

Core Standard: IEC 61008 / IEC 61009

  • Use current-operated type (voltage-type RCDs only for ungrounded systems).

  • Typical settings:

    • Single-device: 30 mA / 0.1 s

    • Large circuits: 50–100 mA

  • Use 3-pole + N type for 3-phase loads to avoid false tripping due to N/E confusion


Previous:no more Next:no more