Writer: admin Time:2025-10-10 14:39:29 Browse:159℃
Core Standard: IEEE Std 32 / IEC 60071-1
The grounding resistance value must balance fault limitation and protection sensitivity. Incorrect selection may cause either excessive fault current or delayed protection operation.
Formula:
: Line voltage or system voltage
: Protection current setting (typically 200–1000 A)
Example:
For a 10 kV system with a 500 A target fault current,
In practice, 12 Ω is commonly used to align with standard resistor element series.
Verification: Neutral-point voltage displacement ≤ 10 % of phase voltage; steady-state temperature rise within rated limits.
Core Standard: IEEE Std C37.101 / IEC 60909
Thermal capacity must match the system’s protection coordination:
Typical distribution networks: Protection clears within 0.2 s → 10 s rating recommended (per IEC type test, 1000 A × 10 s = 5 MJ).
Critical loads (data centers, hospitals): With delayed backup protection (2–3 s), select ≥ 5 s models.
Tip: Certified NGRs clearly mark “1000 A / 10 s” or equivalent; uncertified products may omit this parameter.
Core Standard: ASTM B344 / IEC 60115
Material determines both lifespan and temperature coefficient:
Nickel-Chromium Alloy (NiCr): Temp. coefficient ≤ 50 ppm/°C; withstands 760 K rise for 10–60 s; lifespan > 20 years.
Stainless Steel (304/316L): High corrosion resistance, especially for marine or chemical sites.
Carbon Steel: Low cost but poor oxidation resistance; resistance drift or fuse risk after 1–2 years.
Recommendation:
Indoor/industrial: NiCr alloy balance of cost and performance.
Marine/chemical: 316L stainless steel for corrosion protection.
Core Standard: IEC 60255 / IEC 61850
Modern NGR systems must integrate both protective interlocks and remote supervision:
Basic Protections:
Overcurrent trip (aligned with Iset)
Overtemperature alarm (≥ 300 °C)
Door/isolator interlock
Smart Monitoring:
Current + temperature sensors
RS485 / Modbus-RTU communication
SCADA integration (fault current waveform & temperature trend)
Advanced Options:
Fault counter, remote ON/OFF, event log for predictive maintenance.
Core Standard: IEC 60071-1 / IEC 62271-200 / IEEE Std 32
Insulation and creepage design ensure reliability under environmental stress:
For 10 kV systems:
Creepage ≥ 250 mm
Phase-to-earth insulation ≥ 1000 MΩ (2.5 kV megger)
Phase spacing ≥ 125 mm
Enclosure protection:
Standard type: IP55 (industrial)
Enhanced type: IP65 (mining, offshore)
Material:
304/316L stainless steel (≥ 15 yrs anti-corrosion)
Hot-dip galvanized steel (zinc ≥ 85 µm, 10 yrs + durability)
Explosion-proof option: IEC 60079-1 compliant design.
Core Standard: IEEE Std 142 (Green Book) / IEC 60071
High-Resistance Systems:
1 kΩ – 2 kΩ range, fault current ≤ 10 A; ideal for data centers & hospitals.
Use ±1 % precision metal film resistors.
Low-Resistance Systems:
5 Ω – 50 Ω range, fault current 50 – 1000 A; used in industrial grids.
Use wire-wound resistors ≥ 5 kW.
Hybrid Systems:
With arc-suppression coil + resistor combination; short-time impulse type required, ensuring “arc extinction before resistor insertion.”
Core Standard: IEC 60529 / IEC 60068
Environment determines enclosure and cooling method:
Outdoor / humid: IP54–IP65, sealed cabinet with anti-condensation heater.
Indoor / control room: IP30 adequate, ≥ 5 kW units require forced air cooling + fan fault alarm.
High altitude: Increase insulation rating by 10 % per 1000 m.
Core Standard: IEC 60255-151 / IEEE C37.101
Changing to an NGR (low-resistance grounding) requires relay coordination:
Enable zero-sequence protection.
Adjust pickup ≤ 300 A to coordinate with upstream grid.
Failure to adjust may cause unwanted feeder tripping during faults.
Core Standard: IEC 61727 / IEEE 1547
Distributed sources may alter fault current direction.
Check inverter fault contribution and ensure directional earth-fault relays are used to avoid mal-operation.
Core Standard: IEEE Std 32 / IEC 60076-3
Use a Z-type grounding transformer + NGR combination:
Grounding transformer capacity ≈ (system capacitive current × 10 kV) → e.g. 25 A → 250 kVA.
Zero-sequence impedance ≤ 5 Ω.
No-load loss ≤ 0.5 %; negligible under normal operation.
Verify thermal coordination between the grounding transformer and resistor assembly.
Core Standard: IEC 61008 / IEC 61009
Use current-operated type (voltage-type RCDs only for ungrounded systems).
Typical settings:
Single-device: 30 mA / 0.1 s
Large circuits: 50–100 mA
Use 3-pole + N type for 3-phase loads to avoid false tripping due to N/E confusion

WhatsApp: +86-18631228466
Tel: +86-312-5959618
Email: info@orionresistors.com
Add: No. 79, Fuchang Road, Zhongguancun Entrepreneurship Base, Baoding City,China