+86-312-5959618  info@orionresistors.com
NGR Blog

10 Key Parameters for Selecting Neutral Grounding Resistors

Writer: admin Time:2025-10-10 14:39:29 Browse:160℃


1. How to determine the correct grounding resistance value?

Core Standard: IEEE Std 32 / IEC 60071-1
The grounding resistance value must balance fault limitation and protection sensitivity. Incorrect selection may cause either excessive fault current or delayed protection operation.
Formula:

R=UL3×Iset

  • UL: Line voltage or system voltage

  • Iset: Protection current setting (typically 200–1000 A)

Example:
For a 10 kV system with a 500 A target fault current,

R=100001.732×50011.54Ω

In practice, 12 Ω is commonly used to align with standard resistor element series.
Verification: Neutral-point voltage displacement ≤ 10 % of phase voltage; steady-state temperature rise within rated limits.

2. How to select the thermal withstand time (time rating)?

Core Standard: IEEE Std C37.101 / IEC 60909
Thermal capacity must match the system’s protection coordination:

  • Typical distribution networks: Protection clears within 0.2 s → 10 s rating recommended (per IEC type test, 1000 A × 10 s = 5 MJ).

  • Critical loads (data centers, hospitals): With delayed backup protection (2–3 s), select ≥ 5 s models.
    Tip: Certified NGRs clearly mark “1000 A / 10 s” or equivalent; uncertified products may omit this parameter.

3. Which resistor element material ensures long-term stability?

Core Standard: ASTM B344 / IEC 60115
Material determines both lifespan and temperature coefficient:

  • Nickel-Chromium Alloy (NiCr): Temp. coefficient ≤ 50 ppm/°C; withstands 760 K rise for 10–60 s; lifespan > 20 years.

  • Stainless Steel (304/316L): High corrosion resistance, especially for marine or chemical sites.

  • Carbon Steel: Low cost but poor oxidation resistance; resistance drift or fuse risk after 1–2 years.
    Recommendation:

  • Indoor/industrial: NiCr alloy balance of cost and performance.

  • Marine/chemical: 316L stainless steel for corrosion protection.

4. What protection and monitoring functions are essential?

Core Standard: IEC 60255 / IEC 61850
Modern NGR systems must integrate both protective interlocks and remote supervision:

  • Basic Protections:

    • Overcurrent trip (aligned with Iset)

    • Overtemperature alarm (≥ 300 °C)

    • Door/isolator interlock

  • Smart Monitoring:

    • Current + temperature sensors

    • RS485 / Modbus-RTU communication

    • SCADA integration (fault current waveform & temperature trend)

  • Advanced Options:

    • Fault counter, remote ON/OFF, event log for predictive maintenance.

5. What insulation level and clearance are required for safety?

Core Standard: IEC 60071-1 / IEC 62271-200 / IEEE Std 32
Insulation and creepage design ensure reliability under environmental stress:

  • For 10 kV systems:

    • Creepage ≥ 250 mm

    • Phase-to-earth insulation ≥ 1000 MΩ (2.5 kV megger)

    • Phase spacing ≥ 125 mm

  • Enclosure protection:

    • Standard type: IP55 (industrial)

    • Enhanced type: IP65 (mining, offshore)

  • Material:

    • 304/316L stainless steel (≥ 15 yrs anti-corrosion)

    • Hot-dip galvanized steel (zinc ≥ 85 µm, 10 yrs + durability)

  • Explosion-proof option: IEC 60079-1 compliant design.

6. How to select the right NGR for high-resistance vs. low-resistance grounding systems?

Core Standard: IEEE Std 142 (Green Book) / IEC 60071

  • High-Resistance Systems:
    1 kΩ – 2 kΩ range, fault current ≤ 10 A; ideal for data centers & hospitals.
    Use ±1 % precision metal film resistors.

  • Low-Resistance Systems:
    5 Ω – 50 Ω range, fault current 50 – 1000 A; used in industrial grids.
    Use wire-wound resistors ≥ 5 kW.

  • Hybrid Systems:
    With arc-suppression coil + resistor combination; short-time impulse type required, ensuring “arc extinction before resistor insertion.”

7. How does installation environment affect NGR design?

Core Standard: IEC 60529 / IEC 60068
Environment determines enclosure and cooling method:

  • Outdoor / humid: IP54–IP65, sealed cabinet with anti-condensation heater.

  • Indoor / control room: IP30 adequate, ≥ 5 kW units require forced air cooling + fan fault alarm.

  • High altitude: Increase insulation rating by 10 % per 1000 m.

8. What about system protection coordination and relay settings?

Core Standard: IEC 60255-151 / IEEE C37.101
Changing to an NGR (low-resistance grounding) requires relay coordination:

  • Enable zero-sequence protection.

  • Adjust pickup ≤ 300 A to coordinate with upstream grid.
    Failure to adjust may cause unwanted feeder tripping during faults.

9. Any special considerations for systems with distributed generation (e.g. solar, wind)?

Core Standard: IEC 61727 / IEEE 1547
Distributed sources may alter fault current direction.
Check inverter fault contribution and ensure directional earth-fault relays are used to avoid mal-operation.

10. How to design NGRs for Δ-connected transformers without a neutral point?

Core Standard: IEEE Std 32 / IEC 60076-3
Use a Z-type grounding transformer + NGR combination:

  • Grounding transformer capacity ≈ (system capacitive current × 10 kV) → e.g. 25 A → 250 kVA.

  • Zero-sequence impedance ≤ 5 Ω.

  • No-load loss ≤ 0.5 %; negligible under normal operation.

  • Verify thermal coordination between the grounding transformer and resistor assembly.

11. How should the residual current device (RCD/ELCB) be selected for client protection?

Core Standard: IEC 61008 / IEC 61009

  • Use current-operated type (voltage-type RCDs only for ungrounded systems).

  • Typical settings:

    • Single-device: 30 mA / 0.1 s

    • Large circuits: 50–100 mA

  • Use 3-pole + N type for 3-phase loads to avoid false tripping due to N/E confusion


综合电阻柜logo 压缩.jpg

1762153985201194.jpg