+86-312-5959618  info@orionresistors.com
NGR Blog

What Are the Voltage and Current, and Phase Changes when a Ground Fault Occurs in an Ungrounded System?

Writer: admin Time:2025-09-15 18:05:59 Browse:221℃

Ungrounded neutral systems, also known as isolated neutral systems, are widely used in medium-voltage power networks. 

However, they present certain drawbacks, which can be better understood by analyzing voltage and current behaviors

 during a single-phase-to-ground fault.


In normal operation, each phase conductor (cable or overhead line) has an equivalent capacitance to ground. Since the system

 is three-phase and symmetrical, the capacitances of the three phases are approximately equal, and so are the corresponding 

capacitive currents (Ia, Ib, Ic), which lead their respective phase voltages by 90° and are separated from each other by 120°.

image.png

image.png


When a single-phase-to-ground fault occurs (for example, on phase C), the ground capacitance of the faulted phase is 

short-circuited,making the phase-to-ground voltage of phase C drop to zero. Because the neutral point is isolated, it shifts, 

causing the phase-to-ground voltages of the healthy phases A and B to rise to √3 times their normal value. Consequently, 

the capacitive currents of phases A and B also increase by a factor of √3. At this stage, the phase angle between the capacitive

 currents of A and B becomes 60°.

image.png

 

image.png

From a current flow perspective, the capacitive current from phase A flows through its phase-to-ground capacitance, the earth,

 and the ground fault point of phase C, then returns via phase C to the winding. A similar path applies for phase B. As a result, 

the ground fault point carries the resultant current of phases A and B. By vector summation, since their phase angle difference

 is 60°, the ground fault current is calculated as 3Ia, i.e., three times the single-phase capacitive current, and its direction is opposite

 to the currents of phases A and B.

image.png

Calculation of current: 2xcos30°x3la=2x√3/2x√3la=3la


image.png


According to the standard IEEE Std. 142-2007, the capacitive current at the ground fault point in ungrounded systems 

should not exceed 10 A. This implies that the single-phase capacitive current should be limited to about 3.3 A. If the fault

 current exceeds 10 A, the consequences may be severe, including equipment damage, overvoltage stresses, and difficulties

 in fault detection. Therefore, careful system design and parameter control are essential to ensure safe and reliable operation

 of ungrounded neutral systems.



Related Articles:

How to Accurately Calculate the Neutral Grounding Resistance Value of a Transformer

Global Top 8 Neutral Grounding Resistor (NGR)Manufacturers

Transformer Neutral Grounding Methods and Applications for High-, Medium-, and Low-Voltage Systems

Solid, Resistance, and Ungrounded Systems — Which Is Safer for your Network?

Why Does the Neutral Point of a Large Generator Need to be Reliably Grounded?



综合电阻柜logo 压缩.jpg

1762153985201194.jpg