Writer: admin Time:2025-12-18 16:11:14 Browse:50℃
Based on the parameters provided for the 3.3kV / 10A Neutral Grounding Resistor (NGR), the routine factory tests must strictly adhere to the IEEE-32 standard. For equipment with low voltage but high resistance, the testing focuses on resistance precision and thermal stability under high-temperature conditions.
The following is the professional English translation of the detailed factory test procedures:
This is the most critical test item used to verify the current-limiting capability of the unit.
Testing Requirement: The nominal resistance is 190.50 Ω with an allowable tolerance of ±10%.
Test Example: Measure using a high-precision bridge or a digital micro-ohmmeter. The actual measured value must fall within the range of 171.45 Ω to 209.55 Ω.
Temperature Correction: The ambient temperature must be recorded during testing (referenced to a baseline of 50℃). The measured value is then converted to the resistance at the reference temperature using the temperature coefficient of 0.00094 / ℃.
This test verifies the insulation strength of the resistor cabinet to ensure no breakdown occurs during high-voltage surges.
Testing Standard: Although the system voltage is 3.3 kV, according to IEEE-32 regulations, the factory dielectric test voltage is typically set at 2.25 x Rated Voltage + 2000V, or performed according to the enclosure's insulation class (usually 10kV or higher).
Acceptance Criteria: Apply the test voltage between the resistor elements and the ground for 60 seconds. There should be no signs of flashover or dielectric breakdown during this period.

Operation: Before and after the dielectric test, use a 2500V Megger (insulation resistance tester) to measure the insulation resistance of the resistor elements to ground and the control circuits to ground.
Standard: For 3.3kV equipment, the insulation resistance should typically be no less than 100MΩ.
Resistor Grid Inspection: Inspect the assembly quality of the AISI-304 Stainless Steel Punched Grids. Ensure uniform spacing between plates and no loose connections to prevent short circuits caused by thermal expansion during a 10-second high-current surge.
CT Verification: Perform ratio and polarity tests on the internal Current Transformer (CT) to ensure it accurately captures the 10A ground fault current.
Temperature Rise Limit Verification: Verify that the materials comply with the maximum temperature rise limit of 760℃.
Ingress Protection (IP) Rating: Inspect door seals and ventilation louvers to ensure compliance with indoor or outdoor installation environment requirements.
Nameplate and Markings: Verify that all parameters (voltage, current, resistance, short-time rating) are consistent with the design drawings.
Warning: Since this device is rated for a working time of only 10 seconds, it is crucial to avoid prolonged power-on during preventive testing in the field!
Below is the Factory Acceptance Test (FAT) procedure for a 3.3kV resistor cabinet.

Base Specifications:
Rated Voltage: 3.3 kV/√3
Rated Current: 10 A
Nominal Resistance: 190.50 Ω ± 10%
Procedure: Use a high-precision digital micro-ohmmeter to measure the resistance between the incoming terminal and the grounding terminal of the NGR cabinet.
Sample Data: The actual measured value is 192.4 Ω.
Judgment: The specification requires a tolerance of ±10% (resulting in an allowable range of 171.45 Ω to 209.55Ω). Since 192.4 Ω falls within this range, the unit is deemed Qualified.
Procedure: Apply a power frequency voltage to the entire resistor assembly relative to the ground. Although the system voltage is 3.3 kV, a higher test voltage is required per the IEEE-32 standard to verify insulation integrity.
Sample Data: Apply 10 kV (or 28 kV if the enclosure is rated for 11 kV systems) for a duration of 1 minute.
Judgment: During the test, there shall be no dielectric breakdown or flashover. If none occur, the unit is Qualified.
Since it is often difficult to provide a high-power source capable of maintaining 10A for 10 seconds (the rated time duration) at the factory, a parameter verification method is typically used:
Procedure: Utilize the temperature coefficient (α = 0.00094 /℃) from the specifications to calculate the resistance change at the maximum temperature rise limit.
Calculation Example: When the temperature reaches the maximum rise limit of 760℃:

Judgment: Verify that even at the maximum temperature rise, the resistance increase will not reduce the ground fault current to a level that fails to trigger the protective relays.
Current Transformer (CT) Test: Conduct a ratio and polarity test on the built-in CT (e.g., 20/5A); ensure the ratio error is less than 1%.
Mechanical Inspection: Inspect the spacing between the AISI-304 stainless steel resistor grids. Ensure the gaps are sufficient to prevent short-circuiting due to thermal expansion during the 10-second high-temperature surge.


WhatsApp: +86-18631228466
Tel: +86-312-5959618
Email: info@orionresistors.com
Add: No. 79, Fuchang Road, Zhongguancun Entrepreneurship Base, Baoding City,China